$767.00

The MIC-30 is a hand-held, rugged, easy-to-use, 1 kV class insulation test meter.  The MIC-30 has a wide measurement range, selectable test voltages, and excellent safety features.

  • Insulation resistance measurement to 100 GΩ
  • User selected test voltages: 50, 100, 250, 500, 1000 V in 10 V steps
  • Displays continuous indication of insulation resistance or leakage current
  • Audio beeps every five-second periods to indicate measurement progress
  • Indication of actual test voltage during the measurement
  • Three-lead measurement
  • Continuity measurement of protective and equipotential conductors according to EN 61557-4
  • Low-voltage circuit continuity and resistance measurement:
  • Circuit resistance measurement (<1999 Ω)
  • Audio alert signal if circuit resistance is below 30 Ω
  • Capacitance measurement during measurement
  • Measurement of alternating and direct voltages from 0 to 600 V
  • Automatic measurement in sockets with the UNI-Schuko adapter with possibility of configuring pairs of measured cable
  • Selectable test times (T1, T2 , T3 from 1 to 600 seconds) to measure one or two absorption coefficients
  • Meter conforms to EN 61557

Safety First Features.

  • Automatic discharge of tested object after the insulation resistance measurement completes to remove high voltage charge remaining due to cable capacitance
  • Protection against measuring live objects, measurement will not proceed

Power Supply

  • 4 AA disposable or rechargeable batteries
  • Continuous indication of state of battery charge

Memory Features

  • 990 memory cells to save test results
  • Wireless data transmission to computer using the Bluetooth.

Virtual instrument application of Sonel MIC-30

5 in stock

Electric safety:

  • type of insulation: double, according to EN 61010 – 1 and IEC 61557
  • measurement category: IV 600 V (III 1000 V) according to EN 61010 – 1
  • protection class acc. to EN 60529: IP67

Other technical specifications:

  • power suply: 4 alkaline batteries or or battery package Ni-MH
  • weight: ~2.20 lbs / ~1 kg
  • dimentions: 8.66″ x 3.94″ x 2.36″ / 220 x 100 x 60 mm

Insulation resistance measurement

Measuring range according to EN 61557 – 2 for UN=50 V: 50 kΩ to 250.0 MΩ

Range Resolution Accuracy
0.0 to 999.9 kΩ 0.1 kΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
1.000 to 9.999 MΩ 0.001 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
10.0 to 99.99 MΩ 0.01 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
100.0 to 250.0 MΩ 0.1 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*

*for the WS-04 lead

Measuring range according to EN 61557 – 2 for UN=100 V: 100 kΩ to 500.0 MΩ

Range Resolution Accuracy
0.0 to 999.9 kΩ 0.1 kΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
1.000 to 9.999 MΩ 0.001 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
10.0 to 99.99 MΩ 0.01 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
100.0 to 500.0 MΩ 0.1 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*

*for the WS-04 lead

Measuring range according to EN 61557 – 2 for UN=250 V: 250 kΩ. to 2.000 GΩ

Range Resolution Accuracy
0.0 to 999.9 kΩ 0.1 kΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
1.000 to 9.999 MΩ 0.001 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
10.0 to 99.99 MΩ 0.01 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
100.0 to 999.0 MΩ 0.1 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
1.000 to 2.000 GΩ 0.001 GΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*

*for the WS-04 lead

Measuring range according to PN-EN 61557 – 2 for UN=500 V: 500 kΩ to 20.00 GΩ

Range Resolution Accuracy
0.0 to 999.9 kΩ 0.1 kΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
1.000 to 9.999 MΩ 0.001 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
10.00 to 99.99 MΩ 0.01 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
100.0 to 999.0 MΩ 0.1 MΩ ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]*
1.000 to 9.999 GΩ 0.001 GΩ ±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]*
10.00 to 20.00 GΩ** 0.01 GΩ ±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]*

*for the WS-04 lead
**for the WS-04 lead range to 10 GΩ

Measuring range according to EN 61557 – 2 for UN=1000 V: 1,000 kΩ to 10.00 GΩ

Range Resolution Accuracy
0.0 to 999.9 kΩ 0.1 kΩ ±(3% m.v. + 8 digits)
1.000 to 9.999 MΩ 0.001 MΩ ±(3% m.v. + 8 digits)
10.00 to 99.99 MΩ 0.01 MΩ ±(3% m.v. + 8 digits)
100.0 to 999.0 MΩ 0.1 MΩ ±(3% m.v. + 8 digits)
1.000 to 9.999 GΩ 0.001 GΩ ±(4% m.v. + 6 digits)
10.00 to 99.99 GΩ 0.01 GΩ ±(4% m.v. + 6 digits)
100.0 GΩ 0.1 GΩ ±(4% m.v. + 6 digits)

Continuity measurement of protective and equipotential conductors with the 200 mA current

Measuring range according to EN 61557 – 4: 0.10 to 1,999 Ω

Range Resolution Accuracy
0.00 to 19.99 Ω 0.01 Ω ±(2% m.v. + 3 digits)
20.0 to 199.9 Ω 0.1 Ω ±(2% m.v. + 3 digits)
200 to 1999 Ω 1 Ω ±(4% m.v. + 3 digits)
  • Voltage on open terminals: <8 V
  • Output current at R <2 Ω: ISC >200 mA: ISC >200 mA
  • Compensation of test leads’ resistance
  • Unidirectional current flow

 

Low-voltage and resistance measurement

Range Resolution Accuracy
0.0 to 199.9 Ω 0.1 Ω ±(3% m.v. + 3 digits)
200 to 1,999 Ω 1 Ω ±(3% m.v. + 3 digits)
  • Voltage on open terminals: <8 V
  • Current for closed terminals 5 mA < ISC < 15 mA
  • Sound signal and green LED on when measured resistance < 30 Ω ± 50%
  • Compensation of test leads’ resistance,

Capacitance measurements

Range Resolution Accuracy
1 to 999 nF 1 nF ±(5% m.v. + 5 digits)
1.00 to 9.99µF 0.01µF ±(5% m.v. + 5 digits)
  • Capacitance value displayed during the RISO measurement
  • For test voltages below 100 V and measured resistance below 10 MΩ, unspecified capacitance measurement error

 

Measurement of alternating and direct voltage

Range Resolution Accuracy
0.0 to 299.9 V 0.1 V ±(2% m.v. + 6 digits)
300 to 600 V 1 V ±(2% m.v. + 2 digits)

Frequency range: 45 to 65 Hz

Additional information

Weight 3.5 lbs
Dimensions 6.5 × 12 × 10 in

Reviews

There are no reviews yet.

Be the first to review “MIC-30 Insulation Resistance Meter”

Your email address will not be published. Required fields are marked *